Variable Speed Drive Savings Calculator (Pumps and Fans, Affinity Laws)

Pumps and fans sized for the peak usually run at part flow, with a valve, damper or bypass wasting the difference. Slowing the motor instead saves a great deal of energy because, by the affinity laws, power falls with the cube of speed. This calculator estimates the saving from a duty profile of flows and hours.

Estimates using the emission factors shown. Check the factor source and year for formal reporting.

Inputs

%
%
%
%
%
%
%
%
%
%
$

Results

Cost saved per year
$12,242.32
Energy now
182,850
Energy with the drive
101,235
Energy saved
81,615
Saving
44.64
%
Simple payback
0.7352

    RefENV-EFF-003
    MethodVSD power at flow q: P = P₀·q·[h_s + (1 − h_s)·q²] ÷ η_drive (affinity laws on the system curve); saving = Σ hours × (P_now − P_VSD)
    CurrencyUSD
    Date2026-11-24

    Working

    Money amounts are plain numbers shown in the currency chosen at the top of the page (symbol only; nothing is converted and no exchange rates are used).

    1. Drive power at each flowP = P₀ × q × (h_s + (1 − h_s)·q²) ÷ ηP₀ = 30 kW, h_s = 0, η = 0.97 (see the table)
    2. Annual energyΣ power × hoursnow 182,850 kWh, with drive 101,235 kWh, saving 81,615 kWh
    3. Cost and paybackkWh × price; cost ÷ saving$12,242.32 a year; $9,000.00 ÷ $12,242.32 = 0.7352 years

    Duty profile

    FlowHoursPower now (kW)Power with drive (kW)kWh saved
    100%10003030.93-928
    85%200027.918.9917813
    70%250025.510.6137229
    50%150022.23.8727501

    Static head matters

    On a system with only friction (fans, closed heating and cooling loops) the pressure needed falls with the square of flow, so power falls with the cube: at 50% flow a drive needs about 13% of full power. When part of the head is static, such as lifting water into a tank, the pump must still deliver that head at low flow, so the saving is much smaller. Enter the input power you measure now at each operating point with the present control; with bypass control the power stays near 100% whatever the flow.

    Assumptions and limits

    • Pump or fan efficiency unchanged at reduced speed; drive losses as entered.
    • The duty profile represents a typical year.

    References

    • US Department of Energy, Improving Pumping System Performance: A Sourcebook for Industry, 2nd ed., 2006.
    • US Department of Energy, Improving Fan System Performance: A Sourcebook for Industry, 2003.
    • Karassik, I. J., Messina, J. P., Cooper, P. and Heald, C. C., Pump Handbook, 4th ed., McGraw-Hill, 2008 (affinity laws).

    Questions

    What does a drive save on the example 30 kW fan?
    Over 7,000 hours at the example duty points, energy falls from 182,850 kWh to 101,234 kWh, a 45% saving of 81,615 kWh or 12,242 a year at 0.15 per kWh, so a 9,000 drive pays back in about 9 months.
    Why do savings at 50% flow look so large?
    With no static head, power at half speed is 0.5³ = 12.5% of full power, while a damper or valve at half flow typically still draws 70–80%.

    Results depend on the figures and factors you enter and on the assumptions listed above. Use the factor set your reporting scheme requires. Read the disclaimer.