Efficiency classes
IEC 60034-30-1 defines efficiency classes IE1 (standard) to IE4 (super premium), and IEC TS 60034-30-2 adds IE5. Each class cuts losses by roughly 15–20% compared with the one below, which is a gain of one to three percentage points in efficiency for mid-sized motors. Use the efficiencies at your actual load from the manufacturers' data, not the class minimums. When a motor fails, the cost to compare is the price difference between an efficient new motor and a standard one or a rewind; replacing a working motor early must pay for the whole motor.
Assumptions and limits
- Same shaft load and speed with either motor (a higher-efficiency motor can run slightly faster, which raises the load on fans and pumps).
- Constant load over the running hours.
References
- IEC 60034-30-1, Rotating electrical machines — Part 30-1: Efficiency classes of line operated AC motors (IE code).
- US Department of Energy, Determining Electric Motor Load and Efficiency, Motor Challenge fact sheet, DOE/GO-10097-517.
- US Department of Energy, Premium Efficiency Motor Selection and Application Guide, 2014.
Questions
- What does a 37 kW motor gain going from 92.7% to 94.4% efficiency?
- At 75% load the input falls by 0.54 kW; over 6,000 hours that is 3,235 kWh, or 485 a year at 0.15 per kWh, so a 900 premium pays back in 1.9 years.
- Is a percentage point of efficiency worth it?
- For motors running most of the year, usually yes: running costs dwarf purchase prices, and a 1-point gain at 37 kW saves about 1,900 kWh a year at 6,000 hours.
Results depend on the figures and factors you enter and on the assumptions listed above. Use the factor set your reporting scheme requires. Read the disclaimer.