U-values, R-values and degree days
The U-value (W/m²·K) is the heat flow per square metre per degree of temperature difference; the R-value is its inverse. US R-values are in ft²·°F·h/Btu (R-1 = 0.176 m²·K/W). Heating degree days add up how far the daily mean temperature falls below a base temperature, typically 15.5 °C (60 °F) or 18 °C (65 °F); choose the base that matches when the building actually needs heat. Savings appear only while the building is heated, and air leakage and thermal bridges are not covered by the U-value.
Assumptions and limits
- Steady-state heat loss; solar and internal gains already reflected in the degree-day base.
- U-values are for the whole element including any thermal bridging.
References
- CIBSE, TM41: Degree-days: Theory and Application, Chartered Institution of Building Services Engineers, 2006.
- ASHRAE Handbook — Fundamentals, chapters on heat transmission and energy estimating (degree-day method).
- ISO 6946, Building components and building elements — Thermal resistance and thermal transmittance — Calculation methods.
Questions
- What does insulating 80 m² of wall from U = 1.5 to 0.25 save?
- With 2,200 degree days, 5,280 kWh of heat a year; at 90% boiler efficiency 5,867 kWh of gas, worth 469 at 0.08 per kWh, so 3,500 of work pays back in 7.5 years and avoids about 1,063 kg CO₂e a year.
- How do I convert a US R-value to SI?
- Multiply by 0.1761: R-13 is 2.29 m²·K/W, a U-value of 0.44 W/m²·K.