Getting the inputs right
Use the circuit power of the old fittings including control gear: a twin 36 W fluorescent fitting draws about 72–80 W with a magnetic ballast. Check that the new fittings give enough light (lumens and distribution) for the task; the lumen method calculator helps size them. Longer LED life also cuts maintenance, which can be a significant part of the saving in high ceilings. In air-conditioned buildings less lighting heat also lowers cooling energy, while in heated buildings it slightly raises heating needs; these interactions are not included.
Assumptions and limits
- Hours of use unchanged after the retrofit apart from the controls saving.
- No discounting (see the energy savings payback calculator for NPV).
References
- CIBSE, Guide F: Energy Efficiency in Buildings, Chartered Institution of Building Services Engineers, 2012.
- US Department of Energy, Federal Energy Management Program, Purchasing Energy-Efficient Commercial and Industrial LED Luminaires.
Questions
- What does replacing 200 fittings of 72 W with 36 W LEDs save?
- At 3,000 hours a year, 21,600 kWh: 3,240 at 0.15 per kWh plus 400 of maintenance, so 3,640 a year. At 60 per fitting (12,000) it pays back in 3.3 years.
- How much CO₂ does that avoid?
- About 2,829 kg a year with the UK 2026 grid factor of 0.13096 kg CO₂e/kWh.
Results depend on the figures and factors you enter and on the assumptions listed above. Use the factor set your reporting scheme requires. Read the disclaimer.