Arranging the fittings
Round the number to a grid that suits the room and keep spacing within the maximum spacing-to-height ratio from the luminaire data, typically 1 to 1.5, for even light. Confirm uniformity with lighting design software for important spaces.
Assumptions and limits
- Average illuminance over the working plane; uniformity not checked.
- Utilisation factor from the manufacturer for the actual room index and reflectances.
References
- EN 12464-1, Light and lighting: lighting of work places, indoor.
- CIBSE SLL Lighting Handbook.
Questions
- How many 4000 lm panels for a 12 × 8 m office at 500 lux?
- 25 fittings with UF 0.6 and MF 0.8, giving 500 lx and 8.3 W/m² with 32 W fittings.
- What is the maintenance factor?
- It allows for light output falling with lamp age and dirt between cleaning; 0.8 is typical for LEDs in clean offices.
This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.