Lighting Design Calculator (Lumen Method)

The lumen method is the standard quick way to work out how many light fittings a room needs. It divides the light required on the working plane by the useful light each fitting delivers, allowing for room geometry and dirt or lamp ageing over time.

Inputs

lm

Results

Luminaires required
25
Average illuminance with that number
500
Room index
2.18
Lighting power density (W/m²)
8.33

    RefENG-ELE-009
    MethodN = E·A/(Φ·UF·MF); room index K = L·W/(H_m·(L + W))
    UnitsSI
    Date2026-11-23

    Working

    Calculated in SI base units; inputs are converted from the units you choose.

    1. Room indexK = L·W/(H_m(L + W))K = 2.182
    2. LuminairesN = E·A/(Φ·UF·MF)N = 500 × 96/(4,000 × 0.6 × 0.8) = 25 → 25
    3. Achieved illuminanceE = 500 lx

    Arranging the fittings

    Round the number to a grid that suits the room and keep spacing within the maximum spacing-to-height ratio from the luminaire data, typically 1 to 1.5, for even light. Confirm uniformity with lighting design software for important spaces.

    Assumptions and limits

    • Average illuminance over the working plane; uniformity not checked.
    • Utilisation factor from the manufacturer for the actual room index and reflectances.

    References

    • EN 12464-1, Light and lighting: lighting of work places, indoor.
    • CIBSE SLL Lighting Handbook.

    Questions

    How many 4000 lm panels for a 12 × 8 m office at 500 lux?
    25 fittings with UF 0.6 and MF 0.8, giving 500 lx and 8.3 W/m² with 32 W fittings.
    What is the maintenance factor?
    It allows for light output falling with lamp age and dirt between cleaning; 0.8 is typical for LEDs in clean offices.

    This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.