Power Factor Correction Capacitor Calculator (kvar)

Inductive loads such as motors draw reactive current that loads cables and transformers without doing work, and many tariffs penalise low power factor. This calculator sizes a capacitor bank to reach a target power factor and shows how much current it frees up.

Inputs

Results

Capacitor rating required
110.6
Apparent power before
266.7
Apparent power after
210.5
Line current before
384.9
Line current after
303.9
Capacitance per phase, delta connected (µF)
733.7

    RefENG-ELE-004
    MethodQ_c = P·(tanφ₁ − tanφ₂); C (delta, per phase) = Q_c/(3·2πf·V²)
    UnitsSI
    Date2026-11-23

    Working

    Calculated in SI base units; inputs are converted from the units you choose.

    1. Reactive power to cancelQ_c = P(tanφ₁ − tanφ₂)Q_c = 200 × (0.8819 − 0.3287) = 110.6 kvar
    2. Current reduction384.9 A → 303.9 A
    3. Capacitance (delta)C = Q_c/(3·2πf·V²)C = 733.7 µF per phase

    Harmonics

    Where drives and other non-linear loads are present, capacitors can resonate with the supply. Use detuned (reactor-protected) banks in those installations.

    Assumptions and limits

    • Balanced three-phase load at constant real power.
    • Capacitor rated at the supply voltage.

    References

    • IEC 60831-1, Shunt power capacitors of the self-healing type for AC systems up to 1000 V.
    • IEEE Std 1036, Guide for application of shunt power capacitors.

    Questions

    How many kvar to correct 200 kW from 0.75 to 0.95 power factor?
    About 111 kvar, cutting the current from 385 A to 304 A at 400 V.
    Does power factor correction save energy?
    It reduces current, so cable and transformer losses fall, and it avoids reactive power charges. The motor itself uses the same real power.

    This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.