Harmonics
Where drives and other non-linear loads are present, capacitors can resonate with the supply. Use detuned (reactor-protected) banks in those installations.
Assumptions and limits
- Balanced three-phase load at constant real power.
- Capacitor rated at the supply voltage.
References
- IEC 60831-1, Shunt power capacitors of the self-healing type for AC systems up to 1000 V.
- IEEE Std 1036, Guide for application of shunt power capacitors.
Questions
- How many kvar to correct 200 kW from 0.75 to 0.95 power factor?
- About 111 kvar, cutting the current from 385 A to 304 A at 400 V.
- Does power factor correction save energy?
- It reduces current, so cable and transformer losses fall, and it avoids reactive power charges. The motor itself uses the same real power.
This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.