Battery Backup Time Calculator (UPS and Inverter)

Battery runtime is not simply amp-hours divided by amps. Lead-acid batteries deliver less capacity at high currents, inverters lose energy, and discharging too deeply shortens battery life. This calculator accounts for all three.

Inputs

%
%

Results

Backup time
1.716
Battery current
46.3
Bank capacity needed for the target time
456.9
Usable energy (nominal)
2.4
  • Capacity also falls in cold conditions and with battery age; allow 20 to 25 % margin for design.

RefENG-ELE-008
MethodPeukert: t = H·(C/(I·H))^k × depth of discharge; I = P/(V·η)
UnitsSI
Date2026-11-23

Working

Calculated in SI base units; inputs are converted from the units you choose.

  1. Battery currentI = P/(V·η)I = 1,000/(24 × 0.9) = 46.3 A
  2. Peukert runtime to full discharget = H·(C/(I·H))^kt = 20 × (200/(46.3 × 20))^1.15 = 3.433 h
  3. Usable runtime3.433 × 0.5 = 1.716 h

Peukert effect

A battery rated 200 Ah at the 20-hour rate (10 A) delivers noticeably less at 50 A. The Peukert exponent captures this: about 1.1 to 1.3 for lead-acid and close to 1 for lithium. The calculation applies the exponent, then limits runtime to the usable depth of discharge.

Assumptions and limits

  • Constant power load and nominal bank voltage.
  • Peukert law with the capacity rating period given.

References

  • Peukert, W., 1897.
  • IEEE Std 485, Recommended practice for sizing lead-acid batteries for stationary applications.

Questions

How long will a 24 V 200 Ah battery run a 1 kW load?
About 1.7 hours to 50 % depth of discharge with an AGM battery and a 90 % efficient inverter.
Why are lithium batteries better for backup?
They tolerate 80 to 90 % depth of discharge and lose little capacity at high current, so a smaller bank gives the same runtime.

This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.