Earth Rod (Ground Rod) Resistance Calculator

Earth electrodes need a low enough resistance for protective devices and lightning protection to work. This calculator estimates the resistance of a driven rod, or a row of rods, from soil resistivity and rod dimensions using the standard formulas.

Inputs

Results

Resistance to earth
20.19
Single rod resistance
20.19
Grouping efficiency
100
%

    RefENG-ELE-007
    MethodSingle rod R = ρ/(2πL)·[ln(8L/d) − 1]; rods in line R_n = R·(1 + λa)/n, a = ρ/(2πRs)
    UnitsSI
    Date2026-11-23

    Working

    Calculated in SI base units; inputs are converted from the units you choose.

    1. Single rodR = ρ/(2πL)·[ln(8L/d) − 1]R = 50/(2π × 2.4) × [ln(1,200) − 1] = 20.19 Ω

    Soil is everything

    Resistance is proportional to soil resistivity, which varies a hundredfold between wet clay and dry sand and changes with season. Measure resistivity on site (Wenner method) and confirm the installed electrode with a fall-of-potential test.

    Assumptions and limits

    • Uniform soil; rod top at ground level.
    • Rods in a straight line with equal spacing (BS 7430 factors).

    References

    • BS 7430, Code of practice for protective earthing of electrical installations.
    • IEEE Std 142 (Green Book), Grounding of industrial and commercial power systems.
    • Dwight, H. B., 1936, Calculation of resistances to ground.

    Questions

    What is the resistance of a 2.4 m earth rod?
    About 20 Ω in 50 Ω·m clay with a 16 mm rod. In 300 Ω·m sand it would be about 120 Ω.
    Does doubling the number of rods halve the resistance?
    Not quite, because the rods share the same soil. Two rods spaced at twice their length give about 54 % of a single rod, not 50 %.

    This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.