Transformer Sizing Calculator (kVA)

A transformer must carry the site maximum demand with room for growth, without running too hot. This calculator turns the connected load into a kVA rating using demand factor, power factor and a growth allowance, then picks the next standard size and gives its full load currents.

Inputs

%
%
%

Results

Required rating
533.3
Next standard rating
630 kVA
Primary full load current (standard rating)
33.07
Secondary full load current (standard rating)
909.3
Loading of the standard rating today
70.5
%

    RefENG-ELE-005
    MethodkVA = P·DF·(1 + growth)/(PF·loading limit); I = S/(√3·V)
    UnitsSI
    Date2026-11-23

    Working

    Calculated in SI base units; inputs are converted from the units you choose.

    1. Maximum demand500 kW × 0.8 = 400 kW = 444.4 kVA
    2. With growth and loading limitS = demand·(1 + g)/(PF·limit)S = 533.3 kVA → 630 kVA
    3. Full load currentsI = S/(√3·V)Primary 33.07 A, secondary 909.3 A

    Demand factor

    Not every load runs at full power at once. The demand factor is the ratio of maximum demand to connected load: often 0.6 to 0.8 for commercial buildings and higher for continuous process plants. Use measured data where you have it.

    Assumptions and limits

    • Three-phase transformer at nameplate ambient conditions.
    • Standard IEC preferred ratings.

    References

    • IEC 60076-1, Power transformers: general.
    • IEC 60076-7, Loading guide for mineral-oil-immersed power transformers.

    Questions

    What transformer size for a 500 kW connected load?
    With 80 % demand factor, 0.9 power factor and 20 % growth, about 533 kVA, so a 630 kVA unit.
    What is the secondary current of a 1000 kVA transformer at 400 V?
    About 1443 A.

    This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.