Demand factor
Not every load runs at full power at once. The demand factor is the ratio of maximum demand to connected load: often 0.6 to 0.8 for commercial buildings and higher for continuous process plants. Use measured data where you have it.
Assumptions and limits
- Three-phase transformer at nameplate ambient conditions.
- Standard IEC preferred ratings.
References
- IEC 60076-1, Power transformers: general.
- IEC 60076-7, Loading guide for mineral-oil-immersed power transformers.
Questions
- What transformer size for a 500 kW connected load?
- With 80 % demand factor, 0.9 power factor and 20 % growth, about 533 kVA, so a 630 kVA unit.
- What is the secondary current of a 1000 kVA transformer at 400 V?
- About 1443 A.