Typical limits
IEC 60364 suggests 3 % for lighting and 5 % for other uses from the origin of the installation; the NEC recommends 3 % for a branch circuit and 5 % overall. Motor starting causes a larger transient dip that should also be checked.
Assumptions and limits
- Balanced three-phase load; lumped load at the far end.
- Resistance from IEC 60228 resistivity; approximate formula (no load-angle correction).
References
- IEC 60364-5-52, Selection and erection of electrical equipment: wiring systems, Annex G.
- IEC 60228, Conductors of insulated cables.
Questions
- What is the voltage drop for 63 A over 80 m of 16 mm² copper at 400 V?
- About 9.9 V or 2.5 % at 70 °C and 0.85 power factor.
- How do I reduce voltage drop?
- Use a larger conductor, shorten the run, raise the supply voltage, or improve the power factor of the load.
This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.