Starting current
Direct-on-line starting draws 6 to 8 times full load current for a few seconds, which can dip the supply voltage. Star-delta cuts this to about a third, and soft starters and drives reduce it further.
Assumptions and limits
- Rated voltage and full load; efficiency and power factor from the nameplate or catalogue.
References
- IEC 60034-1, Rotating electrical machines: rating and performance.
- IEC 60034-30-1, efficiency classes.
Questions
- What current does a 15 kW motor draw at 400 V?
- About 28 A at 91 % efficiency and 0.85 power factor.
- How many amps per kW for a three-phase motor?
- Roughly 1.8 to 2 A per kW at 400 V for small and medium motors.
This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.