Motor Full Load Current Calculator

A motor nameplate gives shaft output, but the supply has to provide that plus losses, at the motor's power factor. This calculator gives full load current for cable and breaker selection, and the typical inrush for each starting method.

Inputs

%

Results

Full load current
27.99
Electrical input power
16.48
Apparent power
19.39
Typical starting current
195.9
  • Use the nameplate current for protection and cable sizing where available; codes such as NEC Table 430.250 also prescribe table values.

RefENG-ELE-003
MethodI = P_out / (√3·V·η·PF) (three-phase); starting current = multiple × I_FL
UnitsSI
Date2026-11-23

Working

Calculated in SI base units; inputs are converted from the units you choose.

  1. Input powerP_in = P_out/ηP_in = 15 / 0.91 = 16.48 kW
  2. Full load currentI = P_in/(√3·V·PF)I = 27.99 A
  3. Starting current7 × 27.99 = 195.9 A

Starting current

Direct-on-line starting draws 6 to 8 times full load current for a few seconds, which can dip the supply voltage. Star-delta cuts this to about a third, and soft starters and drives reduce it further.

Assumptions and limits

  • Rated voltage and full load; efficiency and power factor from the nameplate or catalogue.

References

  • IEC 60034-1, Rotating electrical machines: rating and performance.
  • IEC 60034-30-1, efficiency classes.

Questions

What current does a 15 kW motor draw at 400 V?
About 28 A at 91 % efficiency and 0.85 power factor.
How many amps per kW for a three-phase motor?
Roughly 1.8 to 2 A per kW at 400 V for small and medium motors.

This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.