Quick check
With an infinite source, the fault current at the transformer terminals is the full load current divided by the per-unit impedance: a 1000 kVA, 6 % transformer at 400 V gives about 24 kA. Real sources and cables reduce it.
Assumptions and limits
- Three-phase bolted fault; motor contribution and arc resistance ignored.
- Cable resistance at 20 °C (maximum fault); multicore reactance 0.08 mΩ/m.
References
- IEC 60909-0, Short-circuit currents in three-phase AC systems: calculation of currents.
- IEEE Std 551 (Violet Book), Calculating short-circuit currents in industrial and commercial power systems.
Questions
- What is the fault current of a 1000 kVA transformer?
- Roughly 24 kA at the 400 V terminals for 6 % impedance (full load current divided by 0.06), a little less with a real upstream network and before cable impedance reduces it.
- Why does the cable length matter?
- Cable resistance adds to the loop impedance, so fault current falls along the run. That helps breaking capacity but can make protection too slow at the far end.
This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.