Three-Phase and Single-Phase Power Calculator (kW, kVA, Amps)

Switchgear, cables and generators are rated in amps or kVA, while loads are usually quoted in kW. This calculator converts between them for three-phase, single-phase and DC supplies, with the reactive power that power factor correction would need to supply.

Inputs

Results

Current
50.94
Real power
30
Apparent power
35.29
Reactive power
18.59

    RefENG-ELE-002
    MethodP = √3·V·I·PF (three-phase); P = V·I·PF (single-phase); S = P/PF; Q = √(S² − P²)
    UnitsSI
    Date2026-11-23

    Working

    Calculated in SI base units; inputs are converted from the units you choose.

    1. RelationshipP = √3·V·I·PFI = 50.94 A, P = 30 kW
    2. Apparent and reactive powerS = P/PF; Q = √(S² − P²)S = 35.29 kVA, Q = 18.59 kvar

    Quick check

    At 400 V three-phase and 0.85 power factor, each kW draws about 1.7 A. At 230 V single-phase it is about 5.1 A per kW at the same power factor.

    Assumptions and limits

    • Balanced sinusoidal three-phase load; no harmonics.

    References

    • IEC 60038, IEC standard voltages.
    • Electrical power engineering fundamentals.

    Questions

    How many amps is 30 kW at 400 V three-phase?
    About 51 A at 0.85 power factor (43 A at unity).
    What is the difference between kW and kVA?
    kW is real power that does work; kVA is the total that cables and transformers must carry. kW = kVA × power factor.

    This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.