The cube law
Power varies with the cube of speed, so running a fan at 80 % speed uses only about half the power. This is why variable speed drives on fans pay back quickly when demand varies. In practice, fixed system pressure and drive losses reduce the saving somewhat.
Assumptions and limits
- Fan laws apply to the same fan in the same system (fixed system curve, constant density).
- Efficiencies held constant at the new speed.
References
- ISO 5801, Fans: performance testing using standardized airways.
- AMCA Publication 201, Fans and systems.
Questions
- How much power does a fan moving 2 m³/s at 600 Pa need?
- About 1.2 kW of air power and about 2.0 kW motor input at 70 % fan, 95 % drive and 92 % motor efficiency.
- What is a good specific fan power?
- Below about 1.5 to 2 kW per m³/s for a full supply and extract air handler; many regulations set limits in this range.
This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.