Supply Air Flow Rate Calculator (CFM from Load)

The supply airflow to a room is set by its sensible load and how much colder (or warmer) the supply air is than the room. This calculator converts between load and airflow, accounting for air density at the supply temperature and site altitude.

Inputs

Results

Result
1,307 m³/h (769.1 cfm, 363 L/s)
Airflow
1,307
Airflow in L/s
363
Sensible load
5
Supply air density
1.228

    RefENG-HVAC-004
    MethodQ = ρ·V·cp·ΔT, with air density at altitude and supply temperature
    UnitsSI
    Date2026-11-23

    Working

    Calculated in SI base units; inputs are converted from the units you choose.

    1. Supply air densityρ = 1.228 kg/m³; cp = 1.02 kJ/kg·K (moist air)
    2. Heat balanceQ = ρ·V·cp·ΔT5,000 W = 1.228 × 0.363 × 1020 × 11

    Rules of thumb

    In SI, Q (kW) ≈ 1.2 × V (m³/s) × ΔT. In imperial units, Q (Btu/h) ≈ 1.08 × cfm × ΔT (°F) at sea level. At altitude the air is thinner, so more volume is needed for the same load.

    Assumptions and limits

    • Sensible load only; check latent load separately.
    • Moist air cp of 1.02 kJ/kg·K.

    References

    • ASHRAE Handbook, Fundamentals, chapter 18: Nonresidential cooling and heating load calculations.

    Questions

    How much air for a 5 kW room load with 13 °C supply to a 24 °C room?
    About 0.36 m³/s (1,310 m³/h or 770 cfm) at sea level.
    What supply temperature difference is typical?
    8 to 12 K for mixing ventilation in cooling; displacement systems use smaller differences of 3 to 6 K.