Rules of thumb
In SI, Q (kW) ≈ 1.2 × V (m³/s) × ΔT. In imperial units, Q (Btu/h) ≈ 1.08 × cfm × ΔT (°F) at sea level. At altitude the air is thinner, so more volume is needed for the same load.
Assumptions and limits
- Sensible load only; check latent load separately.
- Moist air cp of 1.02 kJ/kg·K.
References
- ASHRAE Handbook, Fundamentals, chapter 18: Nonresidential cooling and heating load calculations.
Questions
- How much air for a 5 kW room load with 13 °C supply to a 24 °C room?
- About 0.36 m³/s (1,310 m³/h or 770 cfm) at sea level.
- What supply temperature difference is typical?
- 8 to 12 K for mixing ventilation in cooling; displacement systems use smaller differences of 3 to 6 K.