CO₂ Based Ventilation Rate Calculator

People breathe out carbon dioxide at a steady rate, so CO₂ is a good marker of how well a room is ventilated for its occupants. This calculator finds the outdoor airflow that keeps CO₂ at a target level, and the steady level a given airflow will reach.

Inputs

Advanced options (1)

Results

Outdoor air required
89.66
Outdoor air per person
8.966
Steady CO₂ with the actual airflow (ppm)
1,287

    RefENG-HVAC-009
    MethodSteady-state mass balance: Q = N·G / (C_in − C_out)
    UnitsSI
    Date2026-11-23

    Working

    Calculated in SI base units; inputs are converted from the units you choose.

    1. Total CO₂ generationN·G10 × 0.0052 L/s = 0.052 L/s
    2. Required outdoor airQ = N·G / (C_in − C_out)Q = 0.052 / (1,000 − 420)×10⁻⁶ = 89.66 L/s

    Generation rates

    The presets assume an average adult producing about 0.0043 L/s of CO₂ per met of activity, so 0.0052 L/s for seated office work. Children produce less, and rates scale with body size. The steady state is reached after a few time constants (room volume divided by airflow).

    Assumptions and limits

    • Well-mixed room at steady state.
    • Outdoor air has constant CO₂; no other CO₂ sources such as combustion.

    References

    • ASHRAE Standard 62.1, informative appendix on CO₂ and ventilation.
    • Persily, A. and de Jonge, L., 2017, Carbon dioxide generation rates for building occupants.

    Questions

    How much fresh air keeps an office at 1000 ppm?
    About 9 L/s (19 cfm) per seated person with 420 ppm outdoors.
    Is 1000 ppm CO₂ harmful?
    No, it is an indicator of ventilation rather than a toxic level, but higher levels are linked with stuffiness and reduced concentration.

    This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.