Enthalpy datum
Enthalpy here is measured from dry air at 0 °C, as on SI charts. Imperial charts use 0 °F, so their Btu/lb values are about 7.7 Btu/lb higher. Differences in enthalpy, which is what load calculations use, are the same either way.
Assumptions and limits
- Ideal-gas mixture of dry air and water vapour (ASHRAE formulation).
- Thermodynamic wet bulb; a sling psychrometer reads close to this.
- Standard atmosphere for altitude.
References
- ASHRAE Handbook, Fundamentals, chapter 1: Psychrometrics.
- Hyland, R. W. and Wexler, A., 1983.
Questions
- What is the dew point at 25 °C and 50 % RH?
- About 13.9 °C, with a wet bulb of 17.9 °C and moisture content of 9.9 g/kg.
- Why does altitude matter?
- Lower pressure means each kilogram of air holds more water at the same relative humidity and occupies more volume, so airflow-based loads change.
This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.