Cooling Coil Load Calculator (Sensible and Latent)

A cooling coil both cools the air (sensible load) and removes moisture (latent load). This calculator splits the two from the air conditions on and off the coil, and gives the condensate flow for drain sizing.

Inputs

%
%

Results

Total cooling load
24.22
Sensible load
15.39
Latent load
8.831
Sensible heat ratio
0.635
Condensate
12.47

    RefENG-HVAC-003
    MethodQ_total = ṁ(h₁ − h₂); Q_sensible = ṁ(1.006 + 1.86W₂)(t₁ − t₂); condensate = ṁ(W₁ − W₂)
    UnitsSI
    Date2026-11-23

    Working

    Calculated in SI base units; inputs are converted from the units you choose.

    1. StatesIn: W = 11.56 g/kg, h = 55.64 kJ/kg. Out: W = 8.575 g/kg, h = 34.73 kJ/kg
    2. Dry air mass flowṁ = V / v₁ṁ = 1.158 kg/s
    3. Total loadQ = ṁ(h₁ − h₂)Q = 24.22 kW
    4. Sensible and latentQ_s = ṁ(1.006 + 1.86W₂)(t₁ − t₂); Q_l = Q − Q_sQ_s = 15.39 kW, Q_l = 8.831 kW

    Sensible heat ratio

    Offices usually have an SHR of 0.7 to 0.85. Humid climates, kitchens and high fresh-air systems have lower SHR, which needs colder coils or reheat to control humidity.

    Assumptions and limits

    • Steady-state coil; condensate leaves at roughly coil temperature (its small enthalpy is ignored).
    • Airflow measured at entering conditions.

    References

    • ASHRAE Handbook, Fundamentals, chapter 1.
    • ASHRAE Handbook, HVAC Systems and Equipment, cooling coils.

    Questions

    What load does 1 m³/s of air need from 26 °C 55 % to 13 °C 92 %?
    About 24 kW total: 15 kW sensible and 9 kW latent (SHR 0.64), with about 12.5 kg/h of condensate.
    How is condensate calculated?
    Dry-air mass flow times the drop in moisture content. Each kilowatt of latent load condenses about 1.5 litres of water per hour.

    This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.