Sensible heat ratio
Offices usually have an SHR of 0.7 to 0.85. Humid climates, kitchens and high fresh-air systems have lower SHR, which needs colder coils or reheat to control humidity.
Assumptions and limits
- Steady-state coil; condensate leaves at roughly coil temperature (its small enthalpy is ignored).
- Airflow measured at entering conditions.
References
- ASHRAE Handbook, Fundamentals, chapter 1.
- ASHRAE Handbook, HVAC Systems and Equipment, cooling coils.
Questions
- What load does 1 m³/s of air need from 26 °C 55 % to 13 °C 92 %?
- About 24 kW total: 15 kW sensible and 9 kW latent (SHR 0.64), with about 12.5 kg/h of condensate.
- How is condensate calculated?
- Dry-air mass flow times the drop in moisture content. Each kilowatt of latent load condenses about 1.5 litres of water per hour.
This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.