Chilled and Heating Water Flow Rate Calculator

Every chilled or heating water system is sized from one equation: flow equals load divided by the heat carried per litre. This calculator gives the flow for water and glycol mixtures, ready for pipe and pump sizing.

Inputs

Results

Volume flow
4.772
Volume flow (m³/h)
17.18
Mass flow
17,176

    RefENG-HVAC-010
    MethodV = Q / (ρ·cp·ΔT)
    UnitsSI
    Date2026-11-23

    Working

    Calculated in SI base units; inputs are converted from the units you choose.

    1. Mass flowṁ = Q/(cp·ΔT)ṁ = 100,000 / (4,192 × 5) = 4.771 kg/s
    2. Volume flowV = ṁ/ρV = 4.772 L/s = 17.18 m³/h = 75.64 US gpm

    Rules of thumb and glycol

    For water, 1 kW at 5 K needs about 0.048 L/s; in US units, 2.4 gpm per ton at a 10 °F rise. Glycol has lower specific heat, so it needs 5 to 15 % more flow for the same load, and its higher viscosity increases pressure drop.

    Assumptions and limits

    • Constant properties at the mean fluid temperature.

    References

    • ASHRAE Handbook, HVAC Systems and Equipment, hydronic heating and cooling.
    • CIBSE Guide C, properties of water and glycol solutions.

    Questions

    What flow does 100 kW of chilled water need at 5 K?
    About 4.77 L/s (17.2 m³/h, 76 US gpm).
    Why use a larger ΔT?
    A larger temperature difference cuts flow, so pipes and pumps are smaller and pumping energy is lower, though coils and chillers must be selected for it.