Air Mixing Calculator (Two Airstreams)

When two airstreams meet, as return air and fresh air do in a mixing box, the result lies on a straight line between them on the psychrometric chart. This calculator does the mass and energy balance properly, so it gives the mixed temperature, humidity and enthalpy rather than a simple average.

Inputs

%
%

Results

Mixed air dry bulb
26.14
Mixed air relative humidity
48.4
%
Mixed humidity ratio
10.23
Mixed enthalpy
52.38
Mixed wet bulb
18.55
Stream 2 share by mass
19.3
%

    RefENG-HVAC-002
    MethodMass and energy balance on dry air: W and h are mass-weighted
    UnitsSI
    Date2026-11-23

    Working

    Calculated in SI base units; inputs are converted from the units you choose.

    1. Dry air mass flowsṁ = V / vṁ₁ = 0.9364 kg/s, ṁ₂ = 0.224 kg/s
    2. Mixed humidity ratio and enthalpyW = Σṁ·W / Σṁ; h = Σṁ·h / ΣṁW = 10.23 g/kg, h = 52.38 kJ/kg
    3. Mixed temperaturet = (h − 2501W)/(1.006 + 1.86W)t = 26.14 °C

    Mixing by mass, not volume

    Warm, humid air is less dense, so weighting by volume introduces a small error. This calculator converts each airflow to dry-air mass first, which is the correct basis.

    Assumptions and limits

    • Adiabatic mixing with no heat gain or loss.
    • Airflows measured at their own conditions.

    References

    • ASHRAE Handbook, Fundamentals, chapter 1, adiabatic mixing of two moist airstreams.

    Questions

    What is the mixed temperature with 20 % fresh air?
    For 80 % return at 24 °C and 20 % outdoor at 35 °C, about 26.1 °C.
    Can mixing cause fog?
    Yes. Mixing very cold outdoor air with warm humid air can produce a supersaturated mixture, which the calculator flags.

    This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.