Typical rates
Offices are usually ventilated by flow per person (around 10 L/s) rather than ACH, which works out at 2 to 6 ACH. Toilets often use 6 to 10 ACH, commercial kitchens 30 or more, and hospital isolation rooms 12 or more. Check the standard that applies to your building.
Assumptions and limits
- Rectangular room; for other shapes compute the volume separately.
- Perfect mixing when interpreting ACH as dilution rate.
References
- CIBSE Guide A, section 1: ventilation and air quality.
- ASHRAE Standard 62.1, Ventilation for acceptable indoor air quality.
Questions
- How much airflow is 6 ACH for a 10 × 8 × 3 m room?
- 1,440 m³/h, which is 400 L/s or about 848 cfm.
- Is a higher ACH always better?
- Not necessarily: it costs fan and heating or cooling energy. Size for the pollutant or occupancy load, using a CO₂ or per-person method.
This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.