Rectangular ducts
A rectangular duct with the same cross-sectional area as a round duct has more friction. The Huebscher equivalent diameter accounts for this, so the rectangular size given here matches the round duct in both airflow and pressure drop. Keep aspect ratios at 4 or below where possible.
Assumptions and limits
- Fully developed turbulent flow in straight duct.
- Air at the given temperature and altitude, standard humidity.
References
- ASHRAE Handbook, Fundamentals, chapter 21: Duct design.
- Huebscher, R. G., 1948, Friction equivalents for round, square and rectangular ducts.
- EN 1506, Ventilation for buildings: sheet metal air ducts of circular section.
Questions
- What size duct for 1800 m³/h at 1 Pa/m?
- About 340 mm round, so use a 355 mm duct; a 2:1 rectangle of about 450 × 225 mm is equivalent.
- Equal friction or velocity method?
- Equal friction is the common choice for low-pressure supply and extract systems. Velocity limits are used for noise-critical branches and for industrial exhaust, which needs a minimum velocity to carry dust.
This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.