Duct Sizing Calculator (Equal Friction or Velocity)

Duct size is a trade-off between fan energy, noise and space. This calculator sizes a duct for a given airflow by the equal friction or velocity method, using an exact friction calculation, then gives the next standard round size and a rectangular duct that carries the same flow at the same friction.

Inputs

Advanced options (3)

Results

Calculated round duct diameter
340.2
Next standard round size (EN 1506)
355 mm (14 in)
Equivalent rectangular duct
447 × 223 mm (17.6 × 8.79 in)
Velocity in the calculated duct
5.501
Friction rate in the calculated duct
1

    RefENG-HVAC-005
    MethodDarcy-Weisbach with Colebrook friction factor; Huebscher equivalent diameter for rectangular ducts
    UnitsSI
    Date2026-11-23

    Working

    Calculated in SI base units; inputs are converted from the units you choose.

    1. Solve diameterFind D where (f/D)·½ρv² equals the target friction rateD = 340.2 mm
    2. CheckRe = ρvD/μ; Colebrook fv = 5.501 m/s, Re = 124,265, f = 0.01867, ΔP/L = 1 Pa/m
    3. Equivalent rectangleD_e = 1.30(ab)^0.625/(a + b)^0.25446.6 × 223.3 mm

    Rectangular ducts

    A rectangular duct with the same cross-sectional area as a round duct has more friction. The Huebscher equivalent diameter accounts for this, so the rectangular size given here matches the round duct in both airflow and pressure drop. Keep aspect ratios at 4 or below where possible.

    Assumptions and limits

    • Fully developed turbulent flow in straight duct.
    • Air at the given temperature and altitude, standard humidity.

    References

    • ASHRAE Handbook, Fundamentals, chapter 21: Duct design.
    • Huebscher, R. G., 1948, Friction equivalents for round, square and rectangular ducts.
    • EN 1506, Ventilation for buildings: sheet metal air ducts of circular section.

    Questions

    What size duct for 1800 m³/h at 1 Pa/m?
    About 340 mm round, so use a 355 mm duct; a 2:1 rectangle of about 450 × 225 mm is equivalent.
    Equal friction or velocity method?
    Equal friction is the common choice for low-pressure supply and extract systems. Velocity limits are used for noise-critical branches and for industrial exhaust, which needs a minimum velocity to carry dust.

    This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.