Adding up a system
Run the calculator for each section of the longest or most resistant path, add the results, then add pressure drops for filters, coils, grilles and terminal units from manufacturer data. That total, at design airflow, is the fan static pressure requirement.
Assumptions and limits
- Constant airflow and density along the section.
- Fitting coefficients referred to the section velocity pressure.
References
- ASHRAE Handbook, Fundamentals, chapter 21.
- CIBSE Guide C, section 4: Flow of fluids in pipes and ducts.
Questions
- What is the pressure drop in 30 m of 355 mm duct at 1800 m³/h?
- About 24 Pa friction (0.81 Pa/m) plus about 23 Pa for fittings with ΣK = 1.5, about 47 Pa in total.
- How much worse is flexible duct?
- Fully stretched flexible duct has several times the friction of galvanised duct, and compressed or sagging flex can be much worse. Keep runs short and straight.