Pump and Fan Affinity Laws Calculator

The affinity laws describe how a centrifugal pump or fan responds to a change in speed or impeller size. They explain why variable speed drives save so much energy: power falls with the cube of speed.

Inputs

Results

New power
4.251
New flow
41.38
New head
27.4
Power saving
43.3
%
  • The laws move a point along a system curve only when that curve passes through zero head. Systems with static head lose more flow than predicted when speed is reduced.

RefENG-FLU-008
MethodQ ∝ N·D; H ∝ N²·D²; P ∝ N³·D³
UnitsSI
Date2026-11-23

Working

Calculated in SI base units; inputs are converted from the units you choose.

  1. Combined ratior = (N2/N1)·(D2/D1)r = 0.8276 × 1 = 0.8276
  2. FlowQ2 = Q1·r41.38 m³/h
  3. HeadH2 = H1·r²27.4 m
  4. PowerP2 = P1·r³4.251 kW

Energy savings

Reducing speed by 20% cuts flow by 20%, head by 36% and power by nearly 50% on a friction-only system. This is the basis for fitting variable frequency drives instead of throttling with a valve.

Assumptions and limits

  • Geometrically similar operating points (same efficiency).
  • Same fluid density.

References

  • Hydraulic Institute, ANSI/HI 1.3.
  • Karassik, I. J., Pump Handbook.

Questions

Do the affinity laws apply to fans?
Yes, the same relations hold for centrifugal and axial fans, with pressure in place of head.
Can I trim an impeller using these laws?
For small trims, yes approximately. For larger trims, use the manufacturer's published curves for each impeller diameter.

This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.