Sprinkler K-Factor Flow and Pressure Calculator

Every sprinkler, spray nozzle and hydrant outlet has a K-factor that links its flow to the pressure at its inlet. This calculator converts between flow and pressure, and between metric and US K-factors.

Inputs

Results

Result
56.57 L/min (14.94 gpm)
Flow
56.57
Pressure
0.5
K-factor in US units (gpm/psi½)
5.55

    RefENG-PLF-002
    MethodQ = K·√P
    UnitsSI
    Date2026-11-23

    Working

    Calculated in SI base units; inputs are converted from the units you choose.

    1. K-factorK = 80 L/min/bar½ = 5.551 gpm/psi½
    2. Discharge equationQ = K·√PQ = 80 × √0.5 = 56.57 L/min

    Metric and US K-factors

    A metric K-factor (L/min per √bar) is about 14.4 times the US value (gpm per √psi). So a K80 sprinkler is the same as a K5.6. Always check the minimum pressure the standard or listing requires, often 0.35 to 0.5 bar (5 to 7 psi).

    Assumptions and limits

    • Pressure is the normal (static minus velocity) pressure at the sprinkler inlet, as used in hydraulic calculations.

    References

    • NFPA 13.
    • EN 12845.

    Questions

    How much water does a K80 sprinkler discharge at 0.5 bar?
    About 56.6 L/min (15 gpm).
    What pressure does a K5.6 head need for 20 gpm?
    About 12.8 psi.

    This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.