Metric and US K-factors
A metric K-factor (L/min per √bar) is about 14.4 times the US value (gpm per √psi). So a K80 sprinkler is the same as a K5.6. Always check the minimum pressure the standard or listing requires, often 0.35 to 0.5 bar (5 to 7 psi).
Assumptions and limits
- Pressure is the normal (static minus velocity) pressure at the sprinkler inlet, as used in hydraulic calculations.
References
- NFPA 13.
- EN 12845.
Questions
- How much water does a K80 sprinkler discharge at 0.5 bar?
- About 56.6 L/min (15 gpm).
- What pressure does a K5.6 head need for 20 gpm?
- About 12.8 psi.
This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.