Expansion Vessel Size Calculator (Heating and Hot Water)

Water expands as a sealed system heats up, and the expansion vessel takes up that extra volume without letting pressure rise to the safety valve setting. This calculator sizes the vessel from the system volume, temperatures, pre-charge and maximum pressure.

Inputs

Results

Minimum vessel nominal volume
42.35
Next standard size
50 L
Expansion volume
15.08
Acceptance factor
0.427
Fluid expansion
3.02
%

    RefENG-PLF-004
    MethodV_n = (V_e + V_wr)·(p_e + 1)/(p_e − p_0) (EN 12828 form); V_e from water density
    UnitsSI
    Date2026-11-23

    Working

    Calculated in SI base units; inputs are converted from the units you choose.

    1. Expansione = ρ(cold)/ρ(hot) − 1e = 3.017 %; V_e = 500 × 0.03017 = 15.08 L
    2. Water reserveV_wr = 3 L
    3. Acceptance factor(p_e − p_0)/(p_e + 1.013)0.427
    4. Nominal volumeV_n = (V_e + V_wr)/AFV_n = 42.35 L

    Pre-charge matters

    The vessel gas cushion must be pre-charged to at least the static head at the vessel, or air can be drawn in at high points. A higher pre-charge reduces the usable volume, so the vessel gets bigger. Set the pre-charge before filling the system.

    Assumptions and limits

    • Isothermal gas compression in the vessel.
    • Water density from 0 to 100 °C; enter expansion directly for glycol.
    • Vessel located at the point the pressures refer to.

    References

    • EN 12828, Heating systems in buildings: design for water-based heating systems.
    • BS 7074-1, Application, selection and installation of expansion vessels.

    Questions

    What size expansion vessel for a 500 litre heating system?
    At 10 to 82 °C with 1 bar pre-charge and 2.5 bar maximum, about 42 L, so a 50 L vessel.
    How much does water expand when heated?
    About 3.0 % from 10 °C to 82 °C, and about 4.3 % to 100 °C.

    This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.