Pre-charge matters
The vessel gas cushion must be pre-charged to at least the static head at the vessel, or air can be drawn in at high points. A higher pre-charge reduces the usable volume, so the vessel gets bigger. Set the pre-charge before filling the system.
Assumptions and limits
- Isothermal gas compression in the vessel.
- Water density from 0 to 100 °C; enter expansion directly for glycol.
- Vessel located at the point the pressures refer to.
References
- EN 12828, Heating systems in buildings: design for water-based heating systems.
- BS 7074-1, Application, selection and installation of expansion vessels.
Questions
- What size expansion vessel for a 500 litre heating system?
- At 10 to 82 °C with 1 bar pre-charge and 2.5 bar maximum, about 42 L, so a 50 L vessel.
- How much does water expand when heated?
- About 3.0 % from 10 °C to 82 °C, and about 4.3 % to 100 °C.
This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.