Long drain lines
The method covers an outlet discharging close to the tank. A long drain pipe adds friction and, if it runs downhill, extra head; in that case treat the outlet as a pipe system and use the pipe pressure drop calculator.
Assumptions and limits
- Constant cross-section tank open to atmosphere.
- Quasi-steady flow; outlet discharges to atmosphere at the tank bottom.
References
- White, F. M., Fluid Mechanics, quasi-steady draining.
Questions
- How long does a 2 m diameter tank with 3 m of water take to drain through a 50 mm valve?
- About 26 minutes with a discharge coefficient of 0.8.
- Why does the last part take so long?
- Flow falls with the square root of the head, so draining the bottom half takes about 2.4 times as long as the top half.
This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.