Sprinkler Water Demand and Tank Size Calculator (Density/Area)

Before a full hydraulic calculation, you need a quick estimate of how much water a sprinkler system will demand and how big the tank must be. This calculator applies the density/area method with a hose allowance and an imbalance margin.

Inputs

%

Results

Estimated total water demand
414
Sprinklers operating
6
Minimum flow per sprinkler
60
Minimum pressure at the most remote sprinkler
0.5625
Water storage for the duration
24.84
  • Preliminary estimate only. Final demand and pressure come from a full hydraulic calculation to NFPA 13, EN 12845 or your local standard, which also sets the minimum end-sprinkler pressure.

RefENG-PLF-003
MethodQ = density × area + hose allowance; storage = Q × duration
UnitsSI
Date2026-11-23

Working

Calculated in SI base units; inputs are converted from the units you choose.

  1. Sprinklers in the design arean = ⌈A / coverage⌉n = ⌈72 / 12⌉ = 6
  2. Minimum flow per sprinklerq = density × coverageq = 5 mm/min × 12 m² = 60 L/min
  3. End-sprinkler pressureP = (q/K)²P = 0.5625 bar
  4. Total demandQ = density × area × (1 + imbalance) + hoseQ = 414 L/min; storage = 24.84 m³

Density and area

Standards set a design density (water per square metre per minute) and an area of operation for each hazard class. The product is the minimum sprinkler demand. Because sprinklers closer to the supply flow more than the minimum, the actual demand is higher; the imbalance allowance covers this for early estimates.

Assumptions and limits

  • All sprinklers in the design area operate.
  • Imbalance allowance approximates the hydraulic calculation result.

References

  • NFPA 13, density/area curves.
  • EN 12845, design criteria by hazard class.

Questions

How much water does an ordinary hazard sprinkler system need?
For 5 mm/min over 72 m² with a 15 % allowance, about 414 L/min, or about 25 m³ for 60 minutes.
What end-sprinkler pressure does a K80 need at 60 L/min?
About 0.56 bar.

This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.