Hot water use
A 12 L/min shower at 40 °C with 60 °C stored water and 10 °C mains uses only 7.2 L/min of hot water. Store hot water at 60 °C or above for Legionella control, and blend down at the outlet with a thermostatic mixing valve.
Assumptions and limits
- Equal density and specific heat for both streams; no heat loss.
References
- HSE L8 and HSG274, Legionnaires' disease: control of legionella bacteria in water systems.
- EN 1111, Sanitary tapware: thermostatic mixing valves.
Questions
- How much hot water does a 40 °C shower use?
- With 60 °C hot and 10 °C cold, 60 % of the flow is hot: 7.2 L/min of a 12 L/min shower.
- What outlet temperature is safe?
- Commonly 41 °C for showers and 43 to 44 °C for basins in care settings; check your local guidance.
This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.