Mixed Water Temperature Calculator (Hot and Cold Blending)

Mixing valves, showers and blending stations combine hot and cold water to a safe outlet temperature. This calculator gives the split of hot and cold flow for a target temperature, or the temperature a given split produces, which also tells you how much stored hot water a shower actually uses.

Inputs

Results

Mixed temperature
40
Hot water share
60
%
Hot water flow
7.2
Cold water flow
4.8

    RefENG-PLF-009
    MethodT_mix = (Q_h·T_h + Q_c·T_c)/(Q_h + Q_c)
    UnitsSI
    Date2026-11-23

    Working

    Calculated in SI base units; inputs are converted from the units you choose.

    1. Energy balancex_hot = (T_mix − T_c)/(T_h − T_c)x = (40 − 10)/(60 − 10) = 0.6
    2. FlowsHot 7.2 L/min, cold 4.8 L/min

    Hot water use

    A 12 L/min shower at 40 °C with 60 °C stored water and 10 °C mains uses only 7.2 L/min of hot water. Store hot water at 60 °C or above for Legionella control, and blend down at the outlet with a thermostatic mixing valve.

    Assumptions and limits

    • Equal density and specific heat for both streams; no heat loss.

    References

    • HSE L8 and HSG274, Legionnaires' disease: control of legionella bacteria in water systems.
    • EN 1111, Sanitary tapware: thermostatic mixing valves.

    Questions

    How much hot water does a 40 °C shower use?
    With 60 °C hot and 10 °C cold, 60 % of the flow is hot: 7.2 L/min of a 12 L/min shower.
    What outlet temperature is safe?
    Commonly 41 °C for showers and 43 to 44 °C for basins in care settings; check your local guidance.

    This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.