Heat-up versus recovery
Heat-up time is from a full tank of cold water to the set temperature. Recovery rate is how many litres per hour the heater can raise from cold feed to set temperature while water is being drawn off. Both depend only on output and temperature rise, not on the shape of the vessel.
Legionella control
Stored hot water is normally kept at 60 °C or above to control Legionella, with distribution at 50 °C or more within a short time at outlets. Check local guidance such as HSG274 in the UK before setting lower temperatures.
Assumptions and limits
- Fully mixed store heated as a single mass.
- Constant heater output; for coils, output falls as the tank warms, so use the output at set temperature.
References
- CIBSE Guide G, Public health and plumbing engineering.
- BS EN 806 and BS 8558, hot water services.
- HSE HSG274 Part 2, Legionella control in hot and cold water systems.
Questions
- How long does a 300 L cylinder take to heat with a 3 kW immersion?
- From 10 to 60 °C, about 6 hours (300 kg × 4.18 kJ/kg·K × 50 K ≈ 17.4 kWh).
- Does the coil output stay constant?
- No, a coil delivers less as the store approaches the primary temperature. Use the coil sizing calculator at the set temperature for a conservative figure.
This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.