When to use it
Hazen-Williams applies to water at ordinary temperatures in turbulent flow. Fire codes (NFPA 13, EN 12845) require it for hydraulic calculations. For hot water, glycol, or other liquids, use Darcy-Weisbach instead.
Assumptions and limits
- Water at about 5 to 25 °C.
- Fittings represented by equivalent length from the applicable standard or manufacturer.
References
- NFPA 13, Standard for the installation of sprinkler systems, hydraulic calculation.
- EN 12845, Fixed firefighting systems: automatic sprinkler systems.
Questions
- What is the friction loss for 1000 L/min in 65 mm steel pipe?
- About 0.054 bar/m in 62.7 mm bore steel with C = 120, so about 3.2 bar over 60 m including fittings. The velocity is 5.4 m/s, so an 80 mm pipe would usually be chosen.
- Why is C = 100 used for dry systems?
- Dry and pre-action pipework corrodes faster internally, so standards assume rougher pipe.