Booster Pump Pressure Calculator (Building Water Supply)

Tall buildings need booster pumps when mains pressure cannot lift water to the top floors with enough pressure left over. This calculator adds up static lift, friction and the pressure needed at the highest outlet, subtracts the inlet pressure, and gives the pump duty head.

Inputs

%

Results

Pump differential pressure
5.32
Pump head
54.35
Pump discharge pressure (gauge)
5.52
Static pressure component
2.937

    RefENG-PLF-008
    MethodΔp = ρg·h_static + friction + residual pressure − inlet pressure
    UnitsSI
    Date2026-11-23

    Working

    Calculated in SI base units; inputs are converted from the units you choose.

    1. Static headρ·g·h2.937 bar
    2. Pressure needed at the pump outlet2.937 + 0.6 + 1.5 = 5.037 bar
    3. Pump differential with margin(5.037 − 0.2) × 1.1 = 5.32 bar = 54.35 m

    Zoning tall buildings

    If the discharge pressure needed for the top floor gives more than about 5 to 6 bar at the bottom floors, split the building into pressure zones or fit pressure-reducing valves.

    Assumptions and limits

    • Water at about 20 °C.
    • Friction losses calculated separately at the design (diversified) flow.

    References

    • EN 806-3, Specifications for installations inside buildings conveying water for human consumption.
    • BS 8558, Guide to the design of water supply systems in buildings.

    Questions

    What pump head do I need for a 30 m high building?
    With 1.5 bar at the top outlet, 0.6 bar of friction and 0.2 bar at the inlet, about 5.3 bar (54 m) including a 10 % margin.
    How much pressure is lost per floor?
    About 0.3 bar (4.3 psi) for each 3 m storey of height, before friction.