Design intensity
Use the rainfall intensity your drainage code requires for the location and return period. Roofs drain quickly, so short-duration intensities (2 to 5 minutes) apply. For large sites, the time of concentration is longer and the design intensity lower.
Assumptions and limits
- Rational method: uniform rainfall over the catchment, peak flow when the whole area contributes.
- Plan area of the roof; add an allowance for wind-driven rain on walls where codes require.
References
- EN 12056-3, Gravity drainage systems inside buildings: roof drainage.
- BS 8515, Rainwater harvesting systems.
Questions
- How much rain runs off a 200 m² roof?
- At 75 mm/h, about 4 L/s peak. With 800 mm of rain a year, about 137 m³ can be harvested.
- What runoff coefficient should I use for a roof?
- 0.9 to 0.95 for metal, tile or membrane roofs; lower for green roofs.
This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.