Cycles of concentration
Evaporation leaves dissolved solids behind. Blowdown removes concentrated water to keep them in check. Raising cycles from 3 to 6 cuts blowdown by 60 %, but needs good water treatment to avoid scale and corrosion.
Assumptions and limits
- Water density 994 kg/m³ and cp 4.18 kJ/kg·K.
- Latent heat at the mean water temperature; evaporative share set by the user.
References
- ASHRAE Handbook, HVAC Systems and Equipment, chapter 40: Cooling towers.
- CTI (Cooling Technology Institute) ATC-105, acceptance test code.
Questions
- How much water does a cooling tower evaporate?
- About 1.5 % of the circulating flow for every 10 K of range, or roughly 0.15 % per kelvin.
- What is a typical approach?
- 3 to 5 K (5 to 10 °F) for HVAC towers. Closer approaches need disproportionately larger towers.
This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.