Pile Group Load Calculator (Axial Load and Moments)

A pile cap shares a column load between its piles, and any moment makes some piles work harder than others. This calculator treats the cap as rigid and the piles as equal vertical springs, so each pile carries an equal share of the vertical load plus a share of each moment in proportion to its distance from the centroid, and flags piles that go into tension.

Inputs

Results

Maximum pile load
508.3
Minimum pile load (negative = uplift)
291.7
Average pile load, P/n
400
Check against capacities
Compression OK; no uplift
Utilisation of the most loaded pile
84.7
%
Number of piles
6
Σx²
5.76
Σy²
2.16
  • Rigid cap, vertical piles of equal stiffness, no lateral load. Check group efficiency, settlement, lateral loads and the cap design separately.

RefENG-STR-036
MethodRigid cap, equal vertical piles: P_i = P/n + M_y·x_i/Σx² + M_x·y_i/Σy²
UnitsSI
Date2026-11-24

Working

Calculated in SI base units; inputs are converted from the units you choose.

  1. Pile coordinates from the group centroidΣx², Σy²6 piles; Σx² = 5.76 m²; Σy² = 2.16 m²
  2. Direct shareP/n2,400 / 6 = 400 kN
  3. Moment sharesΔP = M_y·x/Σx² + M_x·y/Σy²corner pile: 75 + 33.33 kN
  4. Extreme pilesP_max = 508.3 kN; P_min = 291.7 kN

Load on each pile (numbered from the +y row, left to right)

Pilex (m)y (m)x (ft)y (ft)Load (kN)Load (kip)
1-1.20.6-3.9371.969358.380.56
200.601.969433.397.42
31.20.63.9371.969508.3114.3
4-1.2-0.6-3.937-1.969291.765.57
50-0.60-1.969366.782.43
61.2-0.63.937-1.969441.799.29

The rigid cap formula

A rigid cap moves as a plane, so pile shortening, and therefore pile load, varies linearly across the group. Equilibrium then gives P_i = P/n + M_y·x_i/Σx² + M_x·y_i/Σy², the same form as the bolt group and footing formulas. The corner piles on the side of the moment carry the most; if the moment is large enough, piles on the other side go into tension and need to be designed for uplift. Moments can come from column moments, eccentric columns, or horizontal loads acting at the top of the cap.

Assumptions and limits

  • Rigid cap; vertical piles of equal axial stiffness on a rectangular grid.
  • Load and moments referred to the centroid of the group.
  • No lateral load sharing or group efficiency reduction.

References

  • Tomlinson, M. J. and Woodward, J., Pile Design and Construction Practice, pile groups under eccentric loading.
  • Bowles, J. E., Foundation Analysis and Design, pile caps and load distribution.
  • Das, B. M., Principles of Foundation Engineering, pile groups.

Questions

What do the default piles carry?
Six piles (3 × 2 at 1.2 m) under 2,400 kN with moments of 360 and 120 kN·m carry 400 kN each on average. The most loaded corner pile takes 508.3 kN, 85 % of its 600 kN capacity, and the opposite corner 291.7 kN.
When do piles go into tension?
When the moment share exceeds the direct share. For the default group, a moment of 1,920 kN·m increasing the load at +x, with no moment the other way, would bring the row at −x to zero load, and anything more puts it in tension.

This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.