Bolt Group Eccentric Load Calculator (Elastic Method)

Bracket plates, beam splices and seated connections often load a bolt group off its centroid, so the bolts must resist both a direct shear and a twisting moment. This calculator uses the elastic method: every bolt shares the direct load equally and resists the moment in proportion to its distance from the centroid, and the two are added as vectors to find the most heavily loaded bolt.

Inputs

Results

Force on the most loaded bolt, R_max
58.61
Group coefficient, C = P / R_max
2.559
Group capacity, C × bolt capacity
230.3
Utilisation of the critical bolt
65.1
%
Direct shear per bolt, P/n
18.75
Torsional shear on the critical bolt
48.44
Polar sum Σr² (per unit bolt area)
76,250
Number of bolts
8
  • The elastic method is conservative. The instantaneous centre of rotation method used in steel design manuals gives a higher group capacity. Check bolt bearing, tear-out and the plate itself.

RefENG-STR-027
MethodDirect shear P/n plus torsional shear P·e·r/Σr², added as vectors
UnitsSI
Date2026-11-24

Working

Calculated in SI base units; inputs are converted from the units you choose.

  1. Bolt coordinates from the group centroidΣr² = Σ(x² + y²)8 bolts; Σr² = 76,250 mm²
  2. Direct shear (shared equally)R_d = P/nR_d = 150 / 8 = 18.75 kN
  3. Torsional shear (proportional to distance)M = P·e; R_tx = M·y/Σr², R_ty = M·x/Σr²M = 30 kN·m; on bolt 2: R_tx = 44.26 kN, R_ty = 19.67 kN
  4. Vector sum on the critical boltR = √(R_tx² + (R_d + R_ty)²)R_max = 58.61 kN on bolt 2 (x = 50 mm, y = 112.5 mm)
  5. Group coefficient and capacityC = P/R_max; capacity = C·R_boltC = 2.559; capacity = 230.3 kN

Force on each bolt (bolts numbered across each row from the top left; load to the right)

Boltx (mm)y (mm)R (kN)R (kip)
1-50112.544.279.953
250112.558.6113.18
3-5037.514.783.323
45037.541.169.253
5-50-37.514.783.323
650-37.541.169.253
7-50-112.544.279.953
850-112.558.6113.18

Elastic method

Treating the connected plate as rigid and the bolts as equal elastic springs, the moment P·e makes the plate rotate about the centroid of the group. Each bolt then carries a force perpendicular to its radius, equal to P·e·r/Σr². The bolt furthest from the centroid on the side of the load usually governs, because its torsional force adds to the direct shear. The group coefficient C = P/R_max tells you how many bolts' worth of capacity the group really provides.

Assumptions and limits

  • Rigid plate; all bolts the same size and stiffness; vertical load only.
  • Load in the plane of the bolt group (bolts in shear, not tension).
  • Elastic distribution; slip-critical behaviour and bolt hole clearances ignored.

References

  • Salmon, C. G., Johnson, J. E. and Malhas, F. A., Steel Structures: Design and Behavior, eccentrically loaded connections.
  • AISC Steel Construction Manual, Part 7, eccentrically loaded bolt groups (elastic method).
  • Blodgett, O. W., Design of Welded Structures, for the analogous weld group method.

Questions

What is the critical bolt force for the default bracket?
Eight bolts in two lines of four (75 mm pitch, 100 mm gauge) with 150 kN at 200 mm eccentricity give 18.75 kN of direct shear per bolt, and 58.6 kN on the two corner bolts nearest the load. The group coefficient is 2.56, far below the 8 bolts present, because the moment dominates.
What is the capacity of the default group?
With 90 kN per bolt, C = 2.56 gives a group capacity of 230 kN, so the 150 kN load uses 65 % of the critical bolt.

This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.