Resistivity and temperature
Resistance is R = ρL/A: proportional to length, inversely proportional to area. Resistivity is a property of the material: 1.72 × 10⁻⁸ Ω·m for annealed copper by definition of the International Annealed Copper Standard. For metals resistance rises roughly linearly with temperature, about 0.4 % per kelvin for copper, which is why a 100 W lamp filament has a far lower resistance cold than hot. AWG sizes follow d = 0.127 mm × 92^((36 − n)/39).
Assumptions and limits
- Uniform solid conductor carrying DC (no skin effect at high frequency).
- Linear temperature coefficient, adequate over a few hundred kelvin for metals.
- Typical resistivities; alloys and impure metals vary.
References
- IEC 60028, International standard of resistance for copper (annealed copper resistivity 1/58 Ω·mm²/m at 20 °C).
- Serway, R. A. and Jewett, J. W., Physics for Scientists and Engineers, 10th ed., Cengage, 2018, table of resistivities and temperature coefficients.
Questions
- What is the resistance of 100 m of 1 mm copper wire?
- 2.195 Ω at 20 °C, rising to 2.799 Ω at 90 °C.
- What is the resistance of 18 AWG copper?
- An 18 AWG wire is 1.024 mm in diameter, so 100 m has a resistance of 2.095 Ω at 20 °C.
This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.