Plate count
The two end plates do not transfer heat, so they are added to the thermal plates. Manufacturers also choose pass arrangements and plate patterns to balance heat transfer against pressure drop; use this result to compare options before asking for a quotation.
Close approach
Plate exchangers can achieve temperature approaches of 1 to 2 °C, which is why they are popular for heat recovery and district heating substations.
Assumptions and limits
- Pure counter-flow, single pass.
- Constant U and specific heats.
- No phase change.
References
- Incropera and DeWitt, Fundamentals of Heat and Mass Transfer, effectiveness-NTU method.
- Shah, R. K. and Sekulić, D. P., Fundamentals of Heat Exchanger Design.
Questions
- How many plates do I need for 400 kW?
- It depends on flows, temperatures and U. For example, 2 kg/s of water at 90 °C heating 2.5 kg/s from 15 °C, with U = 4000 W/m²·K, needs about 3.1 m², which is 15 plates of 0.25 m² including the two end plates.
- Why is U so much higher than for shell and tube?
- The corrugated plates create strong turbulence at low velocity, giving high film coefficients on both sides.