Heat Exchanger Effectiveness-NTU Calculator

When you know the size of a heat exchanger but not its outlet temperatures, the LMTD method needs trial and error. The effectiveness-NTU method gives the answer directly. Use it to rate existing units, check performance at different flows, or compare flow arrangements.

Inputs

Results

Heat duty
446
Hot outlet temperature
36.78
Cold outlet temperature
50.57
Effectiveness
71
%
Number of transfer units, NTU
1.79
Capacity ratio, C_min/C_max
0.6683

    RefENG-HT-009
    MethodNTU = UA/C_min; ε = f(NTU, C_r, arrangement); Q = ε·C_min·(T_h,in − T_c,in)
    UnitsSI
    Date2026-11-23

    Working

    Calculated in SI base units; inputs are converted from the units you choose.

    1. Capacity ratesC = ṁ·cpC_hot = 8,380 W/K, C_cold = 12,540 W/K; C_r = 0.6683
    2. NTUNTU = UA / C_minNTU = 15,000 / 8,380 = 1.79
    3. Effectiveness for this arrangementε = 0.7097
    4. Duty and outletsQ = ε·C_min·(T_h,in − T_c,in)Q = 446 kW; T_h,out = 36.78 °C, T_c,out = 50.57 °C

    Reading effectiveness

    Effectiveness is the actual duty divided by the maximum possible, which would cool the fluid with the smaller capacity rate all the way to the other inlet temperature. Counterflow always gives the highest effectiveness for a given NTU; parallel flow can never exceed 50 % when both capacity rates are equal.

    Assumptions and limits

    • Constant U and specific heats.
    • No heat loss to surroundings; no phase change unless C_r = 0.

    References

    • Kays, W. M. and London, A. L., Compact Heat Exchangers.
    • Incropera, F. P. et al., Fundamentals of Heat and Mass Transfer, chapter 11.

    Questions

    What NTU gives 90 % effectiveness?
    For counterflow with equal capacity rates, NTU = 9. With C_r = 0.5, about 3.4.
    How do I handle a condenser or boiler?
    A condensing or boiling stream has effectively infinite capacity rate, so C_r = 0 and ε = 1 − e^(−NTU) for any arrangement. Enter a very large mass flow on that side.