Bare Pipe Heat Loss Calculator

A bare hot pipe loses heat by natural convection to the surrounding air and by radiation to nearby surfaces. This calculator works out both, so you can see what an uninsulated run is costing or how much heat an emitter pipe gives off.

Inputs

Results

Heat loss per unit length
208.5
Total heat loss for the length
2.085
Convection coefficient
6.952
Radiation coefficient
6.806
Share lost by radiation
49.5
%

    RefENG-HT-003
    Methodq' = (h_conv + h_rad)·π·D·(Ts − Ta); Churchill-Chu natural convection, Churchill-Bernstein for wind
    UnitsSI
    Date2026-11-23

    Working

    Calculated in SI base units; inputs are converted from the units you choose.

    1. Rayleigh number at film temperatureRa = gβΔT·D³/(να)Ra = 1.016e+6; Nu = 14.57
    2. Coefficientsh_conv = Nu·k/D; h_rad = εσ(Ts² + Ta²)(Ts + Ta)h_conv = 6.952, h_rad = 6.806 W/m²·K
    3. Heat loss per metreq' = (h_conv + h_rad)·π·D·ΔTq' = 13.76 × π × 0.0603 × 80 = 208.5 W/m

    Radiation is not small

    For a painted or rusty pipe indoors, radiation is often about half of the total loss. Bright aluminium or stainless surfaces radiate much less, which is why their losses are lower at the same temperature.

    Assumptions and limits

    • Horizontal pipe in air at atmospheric pressure.
    • Surroundings at ambient temperature for radiation.
    • Pipe surface at uniform temperature.

    References

    • Churchill, S. W. and Chu, H. H. S., 1975.
    • Incropera, F. P. et al., Fundamentals of Heat and Mass Transfer, chapters 7 and 9.
    • CIBSE Guide C, heat emission from bare pipes.

    Questions

    How much heat does a bare 2 inch steel pipe lose at 100 °C?
    About 210 W/m in 20 °C still air with an oxidised surface (emissivity 0.8), roughly half of it by radiation.
    Does wind increase the loss a lot?
    Yes. Even 2 m/s of wind can raise convection several times over still air, so outdoor bare pipes lose much more.

    This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.