Heat Transfer Coefficient in a Pipe Calculator (Forced Convection)

The inside film coefficient is usually the first number you need to size a heat exchanger, coil or jacket. This calculator finds it from the flow rate, tube size and fluid properties, with built-in properties for water and air.

Inputs

Advanced options (1)

Results

Inside heat transfer coefficient
9,000
Reynolds number
63,693
Prandtl number
2.969
Nusselt number
275.8
Dittus-Boelter value (heating) for comparison
8,086

    RefENG-HT-007
    MethodNu from Gnielinski (turbulent), 3.66 or 4.36 (laminar fully developed); h = Nu·k/D
    UnitsSI
    Date2026-11-23

    Working

    Calculated in SI base units; inputs are converted from the units you choose.

    1. Fluid propertiesρ = 983.2 kg/m³, μ = 4.6310e-4 Pa·s, k = 0.6527 W/m·K, cp = 4,184 J/kg·K
    2. Reynolds and Prandtl numbersRe = vD/ν; Pr = μcp/kRe = 63,693; Pr = 2.969
    3. Nusselt numberNu = (f/8)(Re − 1000)Pr / [1 + 12.7√(f/8)(Pr^⅔ − 1)], f = (0.79 ln Re − 1.64)⁻²Turbulent, Gnielinski: Nu = 275.8
    4. Coefficienth = Nu·k/Dh = 275.8 × 0.6527 / 0.02 = 9,000 W/m²·K

    Gnielinski or Dittus-Boelter?

    Dittus-Boelter is the classic textbook equation, but it can be off by 25 % or more. Gnielinski is more accurate across the turbulent range down to Re 3000 and is the default here; Dittus-Boelter is shown for comparison when Re is above 10,000.

    Assumptions and limits

    • Fully developed flow in a smooth round tube.
    • Properties at the bulk temperature; no viscosity correction for wall temperature.

    References

    • Gnielinski, V., 1976, New equations for heat and mass transfer in turbulent pipe and channel flow.
    • Petukhov, B. S., 1970.
    • Incropera, F. P. et al., Fundamentals of Heat and Mass Transfer, chapter 8.

    Questions

    What is the heat transfer coefficient for water in a tube?
    For water at 60 °C flowing at 1.5 m/s in a 20 mm tube, about 9,000 W/m²·K (Dittus-Boelter gives about 8,100).
    How can I increase the film coefficient?
    Increase velocity or use smaller tubes: in turbulent flow h rises with roughly the 0.8 power of velocity, but pressure drop rises faster.

    This calculator is a design aid. Check results against the governing code or standard and have critical work verified by a qualified engineer. Read the disclaimer.