Where the heat goes
Most heat is lost through the covering, so its U-value matters most: a second layer of film or a thermal screen at night cuts losses substantially. Leakage through gaps, vents and doors adds a share that grows with wind. Clear nights add radiant loss to the sky that a simple U-value underestimates, so designers often add a margin. Size the heater on output and buy it on input: a heater rated 160 kW input at 80% efficiency delivers 128 kW.
Assumptions and limits
- Steady-state loss at the design temperatures; solar gain and thermal mass ignored for sizing.
- Air at 1.2 kg/m³ and 1,005 J/kg·K; perimeter and floor losses not counted separately.
- Degree days counted from the inside set point.
References
- ASABE EP406, Heating, Ventilating and Cooling Greenhouses, American Society of Agricultural and Biological Engineers.
- Nelson, P. V., Greenhouse Operation and Management, 7th ed., Pearson, 2012.
- ASHRAE Handbook — Fundamentals, chapter on ventilation and infiltration (sensible heat of air leakage).
Questions
- What heater does a 1,200 m² covering at U = 4 need for 18 °C inside and −5 °C outside?
- About 110 kW through the covering plus 25 kW of leakage at one air change an hour in a 3,200 m³ house: 135 kW output, or 169 kW of heater input at 80% efficiency.
- How do I convert kW to Btu/h?
- Multiply by 3,412: 135 kW is about 461,000 Btu/h.