Greenhouse Heating Calculator (Heat Loss and Heater Size)

Greenhouses lose heat quickly because their covering is thin and they leak air. This calculator sizes the heater for the coldest design night from the covering's U-value and the air leakage rate, and estimates the season's heating energy and cost from heating degree days.

Results are estimates. Follow local agronomy advice and product labels.

Inputs

%

Results

Design heat loss (heater output)
135.1
Through the covering
110.4
By air leakage
24.66
Heater fuel input
168.8
Heat loss per m² of covering
112.5
Seasonal energy input
440.4
Seasonal heating cost
$35,232.00

    RefAGR-AQG-003
    MethodQ = U·A·(Ti − To) + ρ·cp·V·N·(Ti − To)/3600; seasonal energy = (U·A + ρ·cp·V·N/3600) × HDD × 24 h ÷ η
    Currency, unitsUSD, SI
    Date2026-11-24

    Working

    Money amounts are plain numbers shown in the currency chosen at the top of the page (symbol only; nothing is converted and no exchange rates are used). Other quantities are calculated in SI base units and converted from the units you choose.

    1. Conduction through the coveringU × A × ΔT4 × 1,200 m² × 23 K = 110.4 kW
    2. Air leakageρ·cp × V × N ÷ 3600 × ΔT1.2 × 1005 × 3,200 m³ × 1 ÷ 3600 × 23 K = 24.66 kW
    3. Heater sizeoutput = sum; input = output ÷ efficiency135.1 kW output; 135.1 ÷ 0.8 = 168.8 kW input
    4. Season(U·A + ρ·cp·V·N/3600) × HDD × 24 h ÷ η5,872 W/K × 2,500 °C·days × 24 h ÷ 0.8 = 440,400 kWh, costing $35,232.00

    Where the heat goes

    Most heat is lost through the covering, so its U-value matters most: a second layer of film or a thermal screen at night cuts losses substantially. Leakage through gaps, vents and doors adds a share that grows with wind. Clear nights add radiant loss to the sky that a simple U-value underestimates, so designers often add a margin. Size the heater on output and buy it on input: a heater rated 160 kW input at 80% efficiency delivers 128 kW.

    Assumptions and limits

    • Steady-state loss at the design temperatures; solar gain and thermal mass ignored for sizing.
    • Air at 1.2 kg/m³ and 1,005 J/kg·K; perimeter and floor losses not counted separately.
    • Degree days counted from the inside set point.

    References

    • ASABE EP406, Heating, Ventilating and Cooling Greenhouses, American Society of Agricultural and Biological Engineers.
    • Nelson, P. V., Greenhouse Operation and Management, 7th ed., Pearson, 2012.
    • ASHRAE Handbook — Fundamentals, chapter on ventilation and infiltration (sensible heat of air leakage).

    Questions

    What heater does a 1,200 m² covering at U = 4 need for 18 °C inside and −5 °C outside?
    About 110 kW through the covering plus 25 kW of leakage at one air change an hour in a 3,200 m³ house: 135 kW output, or 169 kW of heater input at 80% efficiency.
    How do I convert kW to Btu/h?
    Multiply by 3,412: 135 kW is about 461,000 Btu/h.

    Results depend on the figures you enter and on the assumptions listed above; field, animal and product conditions vary. Read the disclaimer.