Lift is everything
Heat pump COP depends on the temperature lift. Supplying 35 °C underfloor heating from 2 °C outdoor air gives a Carnot COP of about 9.3; supplying 55 °C radiators drops it to about 6.2. Lower flow temperatures make heat pumps far more efficient.
Assumptions and limits
- Reversible cycle between two fixed reservoir temperatures.
- Real-machine fraction is a rough guide; use manufacturer data for design.
References
- Çengel, Y. A. and Boles, M. A., Thermodynamics: An Engineering Approach, chapter 6.
- EN 14511, Air conditioners, chillers and heat pumps: rating conditions.
Questions
- What COP can a heat pump reach?
- For 35 °C flow from 2 °C air, the Carnot COP is about 9.3 and real units achieve roughly 4 to 5.
- Why is power plant efficiency so low?
- With steam at 550 °C and cooling at 30 °C, the Carnot limit is about 63 %; real steam plants reach 40 to 45 %.